Policies & Procedures
back
to listing
FUME
HOOD TESTING CRITERIA
Class
A Fume hoods - High Toxic Hazard
Class B Fume hoods - Moderate Toxic Hazard
Fume hood shall be in normal operation with the usual the usual amount of equipment
in the hood. Testing shall be performed with the sash in the full open
position and hood baffles in the normal position.
For
Class A fume hoods, the average face velocity should
be maintained at 125fpm
For Class B fume hoods, the average face velocity should be maintained at 100fpm
The
average face velocity shall not be less than 100fpm
with hood in normal operating condition for Class
A, and not less than 85fpm for Class B
No
reverse gas flow shall be observed during the use
of the chemical smoke test. This refers to the outward
flow towards the face of the hood.
Face
velocity should not exceed 250fpm at any point on
the face for both Class A and Class B fume hoods.
Establish
and indicate the operating range for monitoring devices.
Mark on fume hood.
Ensure
exhaust duct is functioning properly, and adjust total
exhaust air volume to manufacturers specifications
where applicable.
Ensure
proper working of fan blades and housing.
Adjust
hood baffles and fan drives etc to provide required
face velocity.
Ensure
proper condition and operation of baffles, sash, counter
balance and service fixtures like water, gas, air,
lights etc. Sash must move freely and smoothly and
stay in a stationary position when required.
Ensure
low flow alarm is functional.
Duct
and/or filters must be in proper working condition
with no blockages.
Fume
hoods must operate at minimum noise level
On fulfilling the above criteria a certification
label must be affixed to the fume hood with the
following information: -
Name
of testing organization
Name and signature of person performing testing
Hood application and limitations e.g. perchloric acid
Average and minimum face velocity
Measured exhaust air volume and static pressure
Acceptable range of monitoring device
Date of testing.